i.LON SmartServer Power Line Repeating Network Management Guide 87
d. In the Function box, select the Sundown (
) icon. The calculated sundown time appears in
the Time box, which becomes read-only, and an Offset field is added to the dialog. Verify
that the Offset field is set to 00:00.
e. In the Value box, select #UNLOCK.
f. In the Priority box, enter a priority that is lower than the 255 priority used for the weekday
daily schedule (this example use a priority of 220). This priority essentially locks out the
events in the weekday daily schedule, which have lower priorities (255).
g. Click Close to return to the Edit: <exception start date> dialog. The exception schedule is
updated to reflect the lower priority events that are now scheduled to occur after the
#UNLOCK event at sundown.